1 With ordinary electrical actuator functions, such as the speed and torque adjustable, input and output, sensor position, various protection, fault alarm, etc., function menu English display; as an emergency reset electric control device, some functions of the ordinary actuator need to be closed, such as national torque protection;
2 Reset function: when the external power supply failure, the power supply module automatically cut, restore power supply, emergency drive valve switch, cut off the hazard source; better than the pneumatic, gas-hydraulic dynamic, electric-hydraulic reset function, is a real ideal valve reset product;
3 Daily control / emergency reset function: open all actuator functions as ordinary actuator control valve; use as security reset product in emergency;
4 Self-inspection function: automatically open the pipe valve once (standard 5°) within a certain time interval (6 months) to prevent the valve from corrosion or rust death and ensure the safe reset of the valve in the emergency moment;
5 ESD function: priority ESD function interlocks with SIS system and performs SIS command first in emergency;
6 Field bus (optional): ProfiBUS-RTU, ModBUS, HART;
7 Support wind when there is no power supply, optical power supply and wireless signal transmission control;
Power Supply | 24/48/70VDC
230/110VAC Solar Energy |
Levels of protection | IP68 | Control Method | Wire,Wireless 4/5G Terminal |
LCD Screen | 4 Rows | Input Signal | Analog quantity or switching quantity | Torque detection accuracy | Less than 2%
Can be closed |
Ambient Temperature | -25°~70°
-40°~60° |
Output Signal | 4~20mA ON-OFF Dry/Wet Node | Over torque protection value | 100%
Can be closed |
Ambient Humidity | 98%RH | Communication | ProfiBus-RTU
ModBUS HART SCDAD |
Over temperature protection value | 130° |
Speed Adjustable Range | 15~100% | Position Sensor | Absolute position encoder | Schedule limit protection | Mechanical-electronic double protection |
Torque adjustable range | 10~150% | Power-off-reset response time | 0~300S | Resistance to shock | 600Hz
3 Axis 6g |
Anti-hazard classification | Ex dll C T5 Gb | Single capacitance | 2.7V | working temperature | -40°~70°maximum |
Performance test method | IEC 62391-1 | Capacitive attenuation(Related to the ambient temperature) | 5Years 15~30%
(-30°~50°) |
Cycle charging life | 1 million times Regular cycle charging |